Exciter Model: EXWTG1
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tw2 < 0.5*Mult*TimeStep then Tw2 = 0, ElseIf 0.5*Mult*TimeStep < Tw2 < Mult*TimeStep then Tw2 = Mult*TimeStep
- If 0 < Ta < Mult*TimeStep then Ta = Mult*TimeStep
- If 0 < Tdp < Mult*TimeStep then Tdp = Mult*TimeStep
- If Rmax < Rmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Rexternal > Rmax, then Rmax = Rexternal or if Rexternal < Rmin, then Rmin = Rexternal
Model Equations and/or Block Diagrams
Parameters:
| Ta | Voltage regulator time constant, sec |
| Kdp | Power derivative gain |
| Tdp | Power derivative washout time constant, sec |
| Kw | Speed regulator gain |
| Tw1 | Speed regulator TGR numerator time constant, sec |
| Tw2 | Speed regulator TGR denominator time constant, sec |
| Rmax | Maximum external rotor resistance, pu |
| Rmin | Minimum external rotor resistance, pu |